INPUT |
VOLTAGE(V) |
AC100~120V/200-240V (AC85~132V/170~264V
or DC240~370V), 50/60Hz (44~440Hz or DC) |
CURRENT(A) |
110V ~3.6A,220V ~2.0A |
FREQUENCY |
|
EFFICIENCY |
85 % typ |
INRUSH CURRENT |
20A typ(AC IN 110V, Io=100%),40A typ(AC
IN 220V, Io=100%) at cold start |
OUTPUT |
VOLTAGE(V) |
9 |
CURRENT(A) |
16.7 |
REGULATION,LINE(mV) |
45 Max |
REGULATION,LOAD(mV) |
90 Max |
RIPPLE(mVP-P) |
90 Max |
RIPPLE,NOISE(mVP-P) |
140 Max |
TEMPRETURE DRIFT,0~+50℃(mV) |
135 Max |
RISE TIME(mS) |
200 Max(AC IN 100V, Io=100%) |
HOLDING TIME(mS) |
17 typ (AC IN 100V, Io=100%) |
PROTECTION CIRCUIT |
OVERCURRENT PROTECTION |
Works at over 105% of rating and recovers
automatically |
OVERVOLTAGE PROTECTION |
Works at 115~140% of rating |
ELECTRICALLY ISOLATED |
INPUT-OUTPUT |
AC 3,000V 1 minute current 20mA, DC 500V
100MΩ(At room temperature & Humidity) |
INPUT-CASE,FG |
AC 2,000V 1 minute current 20mA, DC 500V
100MΩ(At room temperature & Humidity) |
OUTPUT-CASE,CASE |
AC 500V 1 minute current 100mA, DC 500V
100MΩ(At room temperature & Humidity) |
ENVIRONMENT |
OPERATING TEMP.AND HUMID. |
-10~+50℃:100%,50~60℃:80%, 20~90% RH(Non
condensing) |
STORAGE TEMP.AND HUMID. |
-20~+75℃, 20~90% RH(Non condensing) |
VIBRATION |
10~55Hz at 1G, 3 minutes period, 30 minutes
along X,Y and Z axis |
IMPACT |
10G for 20ms once on each X,Y and Z axis |
SAFETY |
SAFETY REGULATION |
Complied with UL60950,EN60950 |
LINE CONDUCTED RF VOLTAGE |
Complied with FCC Part15 ,VCCI-A,CISPR22-A,EN55022-A |
|